7. COMMUNICATION DATA LIST
IMR01Y06-E6
46
7.2.1 1 station occupied 1 time (1 controller assignment)
Remote register (RWr)
Data direction: COM-JC (Remote device station) → Master station (PLC)
Data capacity: 4-word
Address Communication item Data range
Factory
set value
RWrn Device address 1 Measured value (PV) Input scale low to
Input scale high
RWrn+1 Manipulated output value
(MV1)
5.0 to
105.0 %
RWrn+2 Unused
RWrn+3 For extended area display
Data corresponding to the
extension number specified by
setting the display extension
number from RYn0 to RYn5.
Remote register (RWw)
Data direction: Master station (PLC) → COM-JC (Remote device station)
Data capacity: 4-word
Address Communication item Data range
Factory
set value
RWwn Device address 1 Set value (SV) Setting limiter low to
Setting limiter high
0
RWwn+1 Event 1 set value Deviation:
−Input span to +Input span
Process and set value:
Input scale low to
Input scale high
Manipulated output value
(MV1/MV2):
−5.0 to +105.0 %
50
RWwn+2 Event 2 set value 50
RWwn+3 For extended area setting
Data corresponding to the
extension number specified by
setting the setting extension
number from RYn6 to RYnB.
When the Set value (SV), Event 1 set value, or Event 2 set value assigned to the Remote
register (RWw) as a fixed value is changed, operation of the extension setting flag (setting
update flag) is also necessary. For details, refer to Extension number for setting
selection processing (P. 24).